Rated Insulation Volts
600/1000V
Electrical Connection
Double Clamp
Operating Time
37 to 47 ms (Coil De-energization and NO Contact Opening), 25 to 55 ms (Coil Energization and NO Contact Closing)
Control Circuit Voltage Limits
0.85 to 1.1 Uc
Mechanical Durability
5 Mcycles
Impulse Withstand Voltage
8 kV
Thermal Amperage
225 A (at 40°C)
Rated Short-Time Withstand Current
1168 A (at 40°C for 10 s), 200 A (at 40°C for 15 min), 477 A (at 40°C for 1 min), 1460 A (at 40°C for 1 s), 674 A (at 40°C for 30 s)
Max. Operating Watts
75 kW (at 1000V), 45 kW (at 220/230/240V), 75 kW (at 380/400V), 75 kW (at 415V), 90 kW (at 440V, 500V, 690V)
Horsepower @ Three Phase - 240V AC
50 hp
Coil Voltage
20 to 60V DC, 24 to 60 V AC
Horsepower @ Three Phase - 208V AC
40 hp
Horsepower @ Three Phase - 480V AC
100 hp
Auxiliary Contact Form
1NO/1NC
Country of Origin (subject to change)
Unknown