Item
Bimetallic Overload Relay 575Vac 14A Iec
Standards
IEC 60947 || BS 4941 || VDE 0660 || NF C 63-650
Relay Application
motor protection
Mechanical Robustness
shocks NO contact10 Gn for 11 ms IEC 60068-2-27 || shocks NC contact10 Gn for 11 ms IEC 60068-2-27 || vibrations NO contact2 Gn, 5 to 300 Hz IEC 60068-2-6 || vibrations NC contact2 Gn, 5 to 300 Hz IEC 60068-2-6
Flame Retardance
V1 conforming to UL 94 || requirement 2 conforming to NF F 16-101 || requirement 2 conforming to NF F 16-102
Auxiliary Contact Composition
1 NO + 1 NC
Operating Altitude
6561.68 ft (2000 m) without derating
Connections - Terminals
screw clamp terminals 1 1.5-4 mm?solid || screw clamp terminals 2 1.5-4 mm?solid || screw clamp terminals 1 0.75-4 mm?flexible without cable end || screw clamp terminals 2 0.75-4 mm?flexible without cable end || screw clamp terminals 1 0.34-2.5 mm?flexible with cable end || screw clamp terminals 2 0.34-1.5 mm?flexible with cable end
Phase Failure Sensitivity
yes IEC 60947-4-1
Ip Degree Of Protection
IP2X conforming to IEC 60529
Thermal Protection Adjustment Range
10-14 A
Fire Resistance
850°C IEC 60695-2-1
Product Or Component Type
differential thermal overload relay
Product Certifications
UL || CSA || UKCA
[Ith] Conventional Free Air Thermal Current
6 A signalling circuit
Associated Fuse Rating
6 A gG signalling circuit VDE 0660 || 6 A gG signalling circuit IEC 60947
Ambient Air Temperature For Operation
-20-55°C without derating IEC 60947 || -30-60°C with derating IEC 60947
[Ue] Rated Operational Voltage
u003c= 690 V power circuit || 690 V AC AC-15 signalling circuit || 250 V DC DC-13 signalling circuit
Network Frequency
u003c= 400 Hz
Power Dissipation Per Pole
2 W
Tightening Torque
1.3 N.m screw clamp terminals Philips No 2 || 1.3 N.m screw clamp terminals flat ? 6 mm || 1.3 N.m screw clamp terminals pozidriv No 2
Thermal Overload Class
class 10A IEC 60947-4-1
Protective Treatment
TC IEC 60068 || TC DIN 50016
Product Compatibility
LC7K || LP4K || LC1K || LP1K
Control Type
Red push-button trip test function || Blue push-button stop and manual reset || selector switch manual or automatic reset
Mounting Support
under contactor || plate, with specific accessories || rail, with specific accessories
Local Signalling
trip indicator Yellow)
[Ui] Rated Insulation Voltage
power circuit 690 V BS 4941 || power circuit 690 V IEC 60947 || power circuit 750 V VDE 0110 group C || power circuit 600 V CSA C22.2 No 14
[Uimp] Rated Impulse Withstand Voltage
6 kV
Ambient Air Temperature For Storage
-40-70°C
Rated Operational Voltage
Less than or Equal to 690 V power circuit, 690 V AC AC-15 signalling circuit, 250 V DC DC-13 signalling circuit
Rated Insulation Voltage
Power circuit 690 V BS 4941, Power circuit 690 V IEC 60947, Power circuit 750 V VDE 0110 group C, Power circuit 600 V CSA C22.2 No 14
Country of Origin (subject to change)
Czechia