Item
Advcntrlunitcl103Ph 1255A 24Vdc
Overload Relay Amp Setting
1.25 to 5 A
Features
Protection against overload and short-circuit, Manual reset, Earth fault protection, Protection against phase failure and phase imbalance, Free of Halogen, Mercury u0026 Pvc, Resistance to Fire, Electrostatic Discharge, Fast Transients, Radiated Fields, Shock u0026 Vibration
Standards
EN 60947-6-2, IEC 60947-6-2, UL 60947-4-1, with phase barrier, CSA C22.2 No 60947-4-1, with phase barrier, CE, CCC, EAC, ASEFA, ATEX, Marine
Ambient Air Temperature For Storage
-40 to 185°F (-40 to 85°C)
Immunity To Microbreaks
3 ms
Typical Current Consumption
130 mA 24 V DC I maximum while closing with LUB12, 220 mA 24 V DC I maximum while closing with LUB32, 220 mA 24 V DC I maximum while closing with LUB38, 60 mA 24 V DC I rms sealed with LUB12, 80 mA 24 V DC I rms sealed with LUB32, 80 mA 24 V DC I rms sealed with LUB38
Resistance To Electrostatic Discharge
8 kV 3 in open air IEC 61000-4-2, 8 kV 4 on contact IEC 61000-4-2
Rated Impulse Withstand Voltage
6 kV IEC 60947-6-2
Load Type
3-phase motor self-cooled
Fixing Mode
Plug-in front face)
Phase Failure Sensitivity
Yes
Device Application
Motor control, Motor protection
Vibration Resistance
2 gn 5 to 300 Hz power poles open IEC 60068-2-6, 4 gn 5 to 300 Hz power poles closed IEC 60068-2-6
Fire Resistance
1760°F (960°C) parts supporting live components IEC 60695-2-12, 1202°F (650°C) IEC 60695-2-12
Immunity To Voltage Dips
70% / 500 ms IEC 61000-4-11
Shock Resistance
10 gn power poles open IEC 60068-2-27, 15 gn power poles closed IEC 60068-2-27
Resistance To Fast Transients
2 kV 3 serial link IEC 61000-4-4, 4 kV 4 all circuits except for serial link IEC 61000-4-4
Operating Altitude
6561.68 ft (2000 m)
Product Compatibility
Power base LUB12, Power base LUB32, Power base LUB38, Power base LUB120, Power base LUB320, Power base LUB380, Reversing contactor breaker LU2B12BL, Reversing contactor breaker LU2B32BL, Reversing contactor breaker LU2B38BL
Thermal Overload Class
Class 10 40 to 60 Hz -13 to 158°F (-25 to 70°C) IEC 60947-6-2, Class 10 40 to 60 Hz -13 to 158°F (-25 to 70°C) UL 508
Rated Insulation Voltage
690 V IEC 60947-6-2, 600 V UL 60947-4-1, 600 V CSA C22.2 No 60947-4-1
Rated Operational Voltage
690 V AC
Product Or Component Type
Advanced control unit
Main Function Available
Protection against overload and short-circuit, Manual reset, Earth fault protection, Protection against phase failure and phase imbalance
Safe Separation Of Circuit
400 V SELV between the control and auxiliary circuits IEC 60947-1, 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1
Protective Treatment
TH IEC 60068
IP Degree Of Protection
IP20 front panel and wired terminals IEC 60947-1, IP20 other faces IEC 60947-1, IP40 front panel outside connection zone IEC 60947-1
Resistance To Radiated Fields
9.14 V/m (10 V/m) 3 IEC 61000-4-3
Product Specific Application
Basic protection and advanced functions, communication
Immunity To Radioelectric Fields
10 V IEC 61000-4-6
Heat Dissipation
2 W control circuit with LUB12, 3 W control circuit with LUB32, 3 W control circuit with LUB38
Motor Power KW
1.5 kW 400 to 440 V AC 50/60 Hz, 2.2 kW 500 V AC 50/60 Hz, 3 kW 690 V AC 50/60 Hz
Control Circuit Voltage
24 V DC
Control Circuit Voltage Limits
20 to 27 V DC 24 V in operation, 14.5 V DC 24 V drop-out
Operating Time
35 ms opening with LUB12 control circuit, 35 ms opening with LUB32 control circuit, 35 ms opening with LUB38 control circuit, 70 ms closing with LUB12 control circuit, 70 ms closing with LUB32 control circuit, 70 ms closing with LUB38 control circuit
Ambient Air Temperature For Operation
-13 to 158°F (-25 to 70°C)
Tripping Threshold
14.2 x Ir +/- 20%
Utilisation Category
AC-44, AC-41, AC-43
Product Certifications
CE, UL, CSA, CCC, EAC, ASEFA, ATEX, Marine
Country of Origin (subject to change)
France