Mounting Orientation
Diaphragm in vertical position. Consult factory for other position orientations.
Pressure Limits
10 psig (68.95 kPa) continuous, 25 psig (172.4 kPa) surge.
Set Point Adjustment
Screw type.
Features
Floating “null†switch supports applications requiring two set point actions such as open and close damper control; Visible set point indicator simplifies operation and trouble shooting; Large diaphragm provides low range accuracy providing precise control
Service
Air and non-combustible, compatible gases.
Electrical Connections
3 screw type, common, normally open and normally closed.
Temperature Limits
-30 to 110°F (-34.4 to 43.3°C).
Electrical Rating
Non-inductive: 2.5 A @ 110 VAC, 1.5 A @ 220 VAC, 1 A @ 24 VDC, 0.5 A @ 110 VAC; Inductive: 1 A @ 110 VAC, 0.5 A @ 220 VAC, 0.5 A @ 24 VDC. (De-rate 70-80% for very slow pressure changes.)
Country of Origin (subject to change)
United States