Item
SERIES LCI INTUMESCENT SEALANT
Standards
ASTM E814 (UL 1479), ASTM E84/UL 723, CAN/ULC-S115
Usage Location
Bottom of Wall, Construction Joint, Through-Penetration
Expansion Temperature
350 Degrees F
For Material Type
All Common Construction Surfaces
Resistance Properties
Meets LEED v3 V4 & V4.1 requirements., no asbestos, no PCB's, no inorganic fibers, Non-halogenated
Application Method
Caulk Gun
For Use On
Blank opening, Bottom of wall, busway, cables, cable tray, duct, Floor to floor, floor to wall, head of wall, metal pipe, multiple penetrants, plastic pipe, wall to wall
Market
Commercial, Industrial, Residential
Flame Spread Rating
Class A
Maximum Application Temperature
100 Degrees F
Fire Resistance Type
Intumescent
Water Activated
Not Applicable
Minimum Application Temperature
35 Degrees F
For Location
Construction Joints, Through Penetrations
Maximum Service Temperature
185 Degrees F
Firestop Type
Sealant/Caulk
Country of Origin (subject to change)
United States