Item
Molded Case Circuit Breaker
Circuit Breaker Actuator
toggle
Circuit Breaker Mounting Style
Unit Mount Lug
Standards
UL, CSA, NEMA, NOM, CE
High Amp Trip Setting
2500 A
Features
Mercury Free, PVC Free
Application
HACR rated Applications, Distribution
Min. Wire Size
3/0 AWG (Cu/Al)
Max. Wire Size
350 kcmil (Cu/Al)
Interrupt Rating
65 kA at 220/240/480V AC, 35 kA at 380/440/415V AC, 18 kA at 500/525V AC, 20 kA at 250/500V DC, 100 kA at 240V AC, 25 kA at 600V AC
Trip Type
Thermal Magnetic
Communication Interface
Modbus, Ethernet
Rated Operational Voltage
600 V AC 50/60 Hz IEC 60947-3
Long Time Pick-Up Adjustment Range
0.25 to 1 x In
Product Or Component Type
Circuit breaker
Tightening Torque
221.27 lbf.in (25 N.m) 0.15 to 0.29 in? (95 to 185 mm?) (AWG 3/0 to 350 kcmil)
Breaking Capacity
100 kA 240 V AC 50/60 Hz UL 489, 65 kA 480 V AC 50/60 Hz UL 489, 25 kA 600 V AC 50/60 Hz UL 489, 20 kA 250 V DC UL 489
Mounting Height
4.5 in (114.30 mm)
Rated Impulse Withstand Voltage
8 kV IEC 60947-2
Product Certifications
UL, CSA, NOM
Number Of Slots
2 auxiliary switch OF plug-in), 1 alarm switch SD plug-in), 1 overcurrent trip switch SDE plug-in), 1 voltage release MN or MX plug-in)
Electrical Connection
Lugs, line, Lugs, load
AWG Gauge
AWG 3/0 to 350 kcmil aluminium/copper terminals
Rated Service Breaking Capacity
65 kA 220/240 V AC 50/60 Hz IEC 60947-2, 35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2, 18 kA 500/525 V AC 50/60 Hz IEC 60947-2, 20 kA 250 V DC IEC 60947-2, 20 kA 500 V DC IEC 60947-2
Protection Type
Overload protection, Short-circuit protection
Operating Altitude
Less than 6561.68 ft (2000 m) without derating, 5000 m with derating
Device Application
Distribution
Ambient Air Temperature For Storage
-58 to 185°F (-50 to 85°C)
Circuit Breaker Application
HACR rated
Local Signalling
Switched off (OFF) 1 trip indicator green)
Network Frequency
50/60 Hz
Utilisation Category
Category A
Rated Insulation Voltage
750 V IEC 60947-2
Power Wire Stripping Length
0.98 in (25 mm)
Magnetic Hold Current
1250 A
Ambient Air Temperature For Operation
28 to 158°F (-2 to 70°C)
Pollution Degree
3 IEC 60947-1
Trip Unit Technology
Thermal-magnetic
Continuous Current Rating
0.8
Mounting Mode
Unit mount lug)
Terminal Identifier
AL250JD
Suitability For Isolation
Yes IEC 60947-2
IP Degree Of Protection
Front cover IP40
Country of Origin (subject to change)
Mexico