Maximum Voltage Rating
690V AC
Standards
CSA C22.2 No 60947-4-1, EN 60947-6-2, IEC 60947-6-2, REACH, RoHS, UL Listed 60947-4-1
Features
Earth fault protection; Protection against overload and short-circuit; Manual reset; Protection against phase failure and phase imbalance; Free of Halogen, Mercury u0026 PVC; Resistance to Fire, Electrostatic Discharge, Fast Transients, Radiated Fields, Shock u0026 Vibration
Overload Relay Amp Setting
8 to 32 A
Use With - Contactors and Starters
Mfr. Series LUA1C Contactors
Body Width - Relay
1.77 in
Body Height - Relay
2.6 in
Body Depth - Relay
2.36 in
Frame / Series / Class / Code
Class 10
Kit Required for Retrofit Mtg.
No
Overload Relay Current Range
8 to 32A
Item - Relay
IEC Style Overload Relay
Overall Height - Relay
2.6 in
Minumum Rated Motor Current Adjustment
8 A
Minimum Operating Temperature
-13 Degrees F
Compatible with Series
TeSys Ultra
Maximum Operating Temperature
158 Degrees F
Compatible with Manufacturer Model Number
LUB32, LUB38
Maximum Rated Motor Current Adjustment
32 A
Compatible Manufacturer Part Number
LUB32, LUB38
Compatible Manufacturer Model Number
LUB32, LUB38
For Use With Mfr. Model Number
LUB32, LUB38
Control Circuit Voltage
24 V DC
Resistance To Radiated Fields
9.14 V/m (10 V/m) 3 IEC 61000-4-3
Typical Current Consumption
220 mA 24 V DC I maximum while closing with LUB32; 220 mA 24 V DC I maximum while closing with LUB38; 80 mA 24 V DC I rms sealed with LUB32; 80 mA 24 V DC I rms sealed with LUB38
Ambient Air Temperature For Storage
-40 to 185°F (-40 to 85°C)
Operating Altitude
6561.68 ft (2000 m)
Shock Resistance
10 gn power poles open IEC 60068-2-27; 15 gn power poles closed IEC 60068-2-27
Rated Operational Voltage
690 V AC
Product Specific Application
Basic protection requirements for motor starters: overload and short-circuit
IP Degree Of Protection
IP20 front panel and wired terminals IEC 60947-1; IP20 other faces IEC 60947-1; IP40 front panel outside connection zone IEC 60947-1
Device Application
Motor control; Motor protection
Control Circuit Voltage Limits
20 to 27 V DC 24 V in operation; 14.5 V DC 24 V drop-out
Product Certifications
CE; UL; CSA; CCC; EAC; ASEFA; ATEX; Marine
Fire Resistance
1760°F (960°C) parts supporting live components IEC 60695-2-12; 1202°F (650°C) IEC 60695-2-12
Phase Failure Sensitivity
Yes
Resistance To Electrostatic Discharge
8 kV 3 in open air IEC 61000-4-2; 8 kV 4 on contact IEC 61000-4-2
Rated Insulation Voltage
690 V IEC 60947-6-2; 600 V UL 60947-4-1; 600 V CSA C22.2 No 60947-4-1
Fixing Mode
Plug-in front face)
Operating Time
35 ms opening with LUB32 control circuit; 35 ms opening with LUB38 control circuit; 70 ms closing with LUB32 control circuit; 70 ms closing with LUB38 control circuit
Thermal Overload Class
Class 10 40 to 60 Hz -13 to 158°F (-25 to 70°C) IEC 60947-6-2; Class 10 40 to 60 Hz -13 to 158°F (-25 to 70°C) UL 508
Protective Treatment
TH IEC 60068
Immunity To Voltage Dips
70% / 500 ms IEC 61000-4-11
Utilisation Category
AC-43; AC-44; AC-41
Product Or Component Type
Standard control unit
Resistance To Fast Transients
2 kV 3 serial link IEC 61000-4-4; 4 kV 4 all circuits except for serial link IEC 61000-4-4
Product Compatibility
Power base LUB32; Power base LUB38; Power base LUB320; Power base LUB380; Reversing contactor breaker LU2B32BL; Reversing contactor breaker LU2B38BL
Main Function Available
Earth fault protection; Protection against overload and short-circuit; Manual reset; Protection against phase failure and phase imbalance
Vibration Resistance
2 gn 5 to 300 Hz power poles open IEC 60068-2-6; 4 gn 5 to 300 Hz power poles closed IEC 60068-2-6
Safe Separation Of Circuit
400 V SELV between the control and auxiliary circuits IEC 60947-1; 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1
Ambient Air Temperature For Operation
-13 to 158°F (-25 to 70°C)
Tripping Threshold
14.2 x Ir +/- 20%
Motor Power KW
15 kW 400 to 440 V AC 50/60 Hz; 15 kW 500 V AC 50/60 Hz; 18.5 kW 690 V AC 50/60 Hz
Heat Dissipation
3 W control circuit with LUB32; 3 W control circuit with LUB38
Immunity To Radioelectric Fields
10 V IEC 61000-4-6
Immunity To Microbreaks
3 ms
Load Type
3-phase motor self-cooled
Rated Impulse Withstand Voltage
6 kV IEC 60947-6-2
Compatible with Manufacturer Model No.
LUB32, LUB38
Compatible with Mfr. Model No.
LUB32, LUB38
For Use with Mfr Model Number
LUB32, LUB38
Compatible Pump Manufacturer Part Number
LUB32, LUB38
Country of Origin (subject to change)
France