Standards
CE, cULus Listed, EAC, EN/IEC 61326-2-3, EU RoHS Directive, NSF ANSI 61, RCM, REACh Regulation, RoHS
Wetted Materials - Transmitters
316L Stainless Steel
Accuracy
+/-0.5% of Full Scale
Range Values - Transmitter
0 to 150
Range Units - Transmitter
psi
Compatible With
Air -40-275 Degrees F (-40-135 Degrees C), Fresh water 32-275 Degrees F (0-135 Degrees C), Gas -40-275 Degrees F (-40-135 Degrees C), Hydraulic oil -40-275 Degrees F (-40-135 Degrees C), Refrigeration fluid -40-275 Degrees F (-40-135 Degrees C)
Housing
316L Stainless Steel
Process Connection Size - Transmitter
1/4 in
Max. Pressure (PSI)
450 psi
Cable Length
Not Applicable
Features
Circularity Profile, Environmental Disclosure, EU RoHS Directive, Green Premium Product, Mercury Free, REACh Free of SVHC, RoHS Exemption Information
For Use With
Air -40-275 Degrees F (-40-135 Degrees C), Fresh water 32-275 Degrees F (0-135 Degrees C), Gas -40-275 Degrees F (-40-135 Degrees C), Hydraulic oil -40-275 Degrees F (-40-135 Degrees C), Refrigeration fluid -40-275 Degrees F (-40-135 Degrees C)
IP Rating
IP65, IP67, IP69K
Process Connection Size
1/4 in
Housing Material
Stainless Steel
Process Connection Gender
Male
Storage Temperature Range
-58 Degrees F to 212 Degrees F (-50 Degrees C to 100 Degrees C)
Maximum Operating Temperature
185 Degrees F
Minimum Operating Temperature
-22 Degrees F
Electrical Connection
4-Pin M12 Connector
For Use With Media Type
Air 40 Degrees F to 275 Degrees F (-40 Degrees C to 135 Degrees C), Fresh Water 32 Degrees F to 275 Degrees F (0 Degrees C to 135 Degrees C), Gas 40 Degrees F to 275 Degrees F (-40 Degrees C to 135 Degrees C), Hydraulic Oil 40 Degrees F to 275 Degrees F (-40 Degrees C to 135 Degrees C), Refrigeration Fluid 40 Degrees F to 275 Degrees F (-40 Degrees C to 135 Degrees C)
Process Connection Type
NPT
Electrical Connections
4-Pin M12 Connector
Process Media Temperature - Maximum
185 Degrees F
Pressure Measurement - Minimum
0 psi
Process Media Temperature - Minimum
-22 Degrees F
Intrinsic Safety
Not Specified Intrinsically Safe
Hazardous Location Specification
Not Applicable
Includes NIST-Traceable Calibration Certificate
No NIST-Traceable Calibration Certificate Included
Pressure Type Measured
Gauge
Pressure Measurement - Maximum
150 psi
Country of Origin (subject to change)
China