Input or Control Voltage
24 V AC/DC
AC Contact Rating - Relay
4.0 A@240 VAC
DC Contact Rating - Relay
4.0 A@24 VDC
Output Switch Configuration - Relay
(2) NO and (1) NC
Input Power Consumption (Burden)
50 mW
Number of Inputs - Relay
2
Use With - Relay
Coded Magnetic Safety Interlock Switch, E Stop, Limit Switch, Rope Pulls, Light Curtain (OSSD) All Easy Series Relays, Two Hand Control
Environmental Protection
Finger-Safe
Connection Type
M3 screw terminals
Response Time - Relay
50 msec
Standards
CE Certified, CSA Certified, IEC Rated, UL Listed
Electrical Connection - Relay
Plug-In Screw Terminals
Item
Safety Monitoring Relay
For Use With
Coded Magnetic Safety Interlock Switch, Emergency Stop, Light Curtain (OSSD) all Easy Series Relays, Limit Switch, Rope Pulls, Two Hand Control
Contact Rating (DC)
4 A @ 24V
Contact Rating (AC)
4 A @ 24V
Application
Emergency Stops, Gate Enable Device, Light Curtain (OSSD), Rope Pulls, Safety Switches, Two-Hand Control Stations
Electrical Connection
Screw Terminal, Terminal Block Removable
Minimum Operating Temperature
-4 Degrees F
Maximum Operating Temperature
131 Degrees F
Output Switch Configuration
(1) NC, (2) NO
Static Heat Dissipation, Non-Current-Dependent Pvs
5.16 W
Operating Voltage At Ac, 60 Hz - Min
24 V
Supply Voltage At Ac, 50 Hz - Min
24 V
Recovery Time
u003c 1000 ms
Control Voltage 2 - Max
24 V
Stripping Length (Main Cable)
7 mm
Number Of Outputs (Safety Related, Undelayed) With Contact
2
Heat Dissipation Per Pole, Current-Dependent Pvid
0 W
Supply Voltage At Ac, 60 Hz - Min
24 V
Fitted With
Approval according to UL; Detachable clamps; Feedback circuit; Approval for TÜV
Operating Voltage At Ac, 50 Hz - Max
24 V
Safety Performance Level (En Iso 13849-1)
Level e
Number Of Outputs (Signaling Function, Undelayed, Semiconductors)
0
Tightening Torque
0.6 Nm, Screw terminals
Features
Reinforced insulation; Automatic start; 2 Non-delayed enable current paths; Basic insulation; Monitoring of external contactor/expansion unit; Safe insulation
Switching Frequency
Max. 0.5 Hz, Input data
Rated Insulation Voltage (Ui)
250 V
Number Of Outputs (Safety Related, Undelayed, Semiconductors)
0
Climatic Proofing
Dry heat to IEC 60068-2-2; Damp heat, constant, to IEC 60068-2-3
Switching Capacity
5 A at 3600 O/h, AC-15 at 230 V, Outputs; In accordance with IEC 60947-5-1, Outputs; 0.4 W; 5 A at 3600 O/h, DC-13 at 24 V, Outputs
Rated Control Supply Voltage (Us) At Dc - Max
24 V
Resistance
22 Ω (impedance)
Uninterrupted Current
6 A N/O, Limiting continuous current; 6 A N/C, Limiting continuous current
Type
Feedback circuit; Protective door
Breaking Power
110 W max., resistive load (τ = 0 ms), at 110 V DC; 42 W max., inductive load (τ = 40 ms), at 110 V DC; 42 W max., inductive load (τ = 40 ms), at 220 V DC; 144 W max., resistive load (τ = 0 ms), at 24 V DC; 288 W max., resistive load (τ = 0 ms), at 48 V DC; 42 W max., inductive load (τ = 40 ms), at 24 V DC; 1500 VA, max., resistive load (τ = 0 ms), at 250 V AC; 42 W max., inductive load (τ = 40 ms), at 48 V DC; 88 W max., resistive load (τ = 0 ms), at 220 V DC
Operating Temperature - Min
-20 °C
Control Voltage 1 - Max
24 V
Stop Category (IEC 60204)
0
Lifespan, Mechanical
10,000,000 Operations
Relative Humidity
u003c 75 %
Degree Of Protection
IP20; Terminals: IP20; Installation location: ≥ IP54; Enclosure: IP20
Supply Voltage At Ac, 50 Hz - Max
24 V
Product Length/Depth
114.5 mm
Functions
2-channel; Two-hand function
Environmental Conditions
Condensation: Non-condensing; Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2, No. 14-95
Control Voltage 1 Type
AC/DC
Product Name
Eaton ESR5 Safety relay
Power Loss
Normally 5.16 W
Vibration Resistance
10 - 150 Hz, Amplitude: 0.15 mm, Acceleration: 2 g, (IEC/EN 60068-2-6)
Heat Dissipation Capacity Pdiss
0 W
Control Voltage 2 Type
AC/DC
Safety Demands Class Type (En 574)
Type III C
Supply Voltage At Dc - Min
24 V
Control Voltage 1 - Min
24 V
Short-Circuit Current
2.3 A, Input data
Operating Voltage At Ac, 50 Hz - Min
24 V
Number Of Outputs (Signaling Function, Undelayed) With Contact
1
Inrush Current
0.025 - 6 A
Led Indicator
Status indication of SmartWire-DT network: Green LED
Screwdriver Size
0.6 x 3.5 mm, Terminal screws; 2, Terminal screw, Pozidriv screwdriver
Rated Operational Voltage
24 V AC/DC (power supply); 230 V AC; Approx. 24 V DC at input, starting and feedback circuit
Short-Circuit Protection
Short-circuit proof, 24 V, Fuse for control circuit supply, Control circuit; Fuse 6 A gL/gG, For output circuits, External
Rated Impulse Withstand Voltage (Uimp)
6000 V AC
Operating Voltage At Dc - Min
24 V
Control Voltage 2 - Min
24 V
Interference Immunity
According to EN 61000-6-2
Operating Voltage At Ac, 60 Hz - Max
24 V
Air Pressure
795 - 1080 hPa (operation)
Current Consumption
60 mA, DC; 125 mA, AC
Input
u003c 500 ms, Simultaneity for inputs 1/2
Number Of Outputs (Safety Related, Delayed, Semiconductors)
0
Rated Control Supply Voltage (Us) At Ac, 50 Hz - Min
0 V
Pick-Up Time
50 ms typ. (at Uₑ in automatic mode); 50 ms typ. (K1, K2 - for UN automatic mode); 50 ms typ. (K1, K2 - for UN manual operation); 50 ms typ. (at Uₑ in manual mode)
Ambient Storage Temperature - Max
70 °C
Mounting Method
Rail mounting possible; Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Material
Contacts: silver tin oxide, gold plated (AgSnO2, 0.2 µm Au); Enclosure: Polyamide (PA), not reinforced
Protection
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Ambient Operating Temperature - Max
55 °C
Ambient Storage Temperature - Min
-40 °C
Operating Temperature - Max
55 °C
Terminal Capacity
1 x (0.2 - 2.5) mm², solid; 2 x (0.2 - 1) mm², solid; 2 x (0.25 - 1) mm², flexible with ferrule; 24 - 12 AWG, solid or stranded; 1 x (0.25 - 2.5) mm², flexible with ferrule
Short-Circuit Protection Rating
6A gL/gG, NEOZED (N/C), Output fuse, External, Output data; 10A gL/gG, NEOZED (N/O), Output fuse, External, Output data
Input Switch Function Type
Normally closed contact and normally open contact
Electric Connection Type
Screw connection
Number Of Outputs (Safety Related, Delayed) With Contact
0
Rated Control Supply Voltage (Us) At Ac, 60 Hz - Max
24 V
Permissible Total Cable Resistance
50 Ω (input and starting circuits for UN)
Number Of Outputs (Signaling Function, Delayed) With Contact
0
Equipment Heat Dissipation, Current-Dependent Pvid
0 W
Power Supply Circuit
3 W (AC operated 50/60 Hz); 1.5 W (DC operated)
Rated Control Supply Voltage (Us) At Dc - Min
0 V
Number Of Outputs (Signaling Function, Delayed, Semiconductors)
0
Safety Parameter (Iec 62061)
SILCL 3, Safety integrity level claim limit; EN 574 Type III C; SIL 3, Safety integrity level, In accordance with IEC 61508; Cat. 4, Category; 12.1 x 10-10, PFHd, Probability of failure per hour; SIL 3, Safety integrity level
Supply Voltage At Ac, 60 Hz - Max
24 V
Safety Parameter (En Iso 13849-1)
PL e, Performance level; 300,000 switching cycles, B10d; Cat. 4, Category
Rated Control Supply Voltage (Us) At Ac, 50 Hz - Max
24 V
Ambient Operating Temperature - Min
-20 °C
Operating Voltage At Dc - Max
24 V
Rated Operational Current For Specified Heat Dissipation (In)
12A
Rated Control Supply Voltage (Us) At Ac, 60 Hz - Min
20.4 V
Suitable For
Safety functions; Module used to safely interrupt electrical circuits; Safety relay for monitoring two-hand control per EN 574 Type IIIC and protective door switches
Supply Voltage At Dc - Max
24 V
Country of Origin (subject to change)
Germany