Item
Gold Flashed Contact Block W/Dust Protec
Standards
CSA C22.2 No 14 || UL 508 || EN/IEC 60947-5-1 || EN/IEC 60947-5-4 || EN/IEC 60947-1 || JIS C8201-5-1 || JIS C8201-1
Connections - Terminals
screw clamp terminals, u003c= 2 x 1.5 mm² with cable end EN 60947-1 || screw clamp terminals, u003e= 1 x 0.22 mm² without cable end EN 60947-1
Shock Resistance
30 gn 18 ms) half sine wave acceleration IEC 60068-2-27 || 50 gn 11 ms) half sine wave acceleration IEC 60068-2-27
Vibration Resistance
5 gn 2-500 Hz)IEC 60068-2-6
[Ith] Conventional Free Air Thermal Current
10 A EN/IEC 60947-5-1
Contacts Material
gold flashed (Ag/Ni/Au) contacts
Mechanical Durability
10000000 cycles
Tightening Torque
0.8-1.2 N.m EN 60947-1
[Ie] Rated Operational Current
3 A 240 V, AC-15, A600 EN/IEC 60947-5-1 || 6 A 120 V, AC-15, A600 EN/IEC 60947-5-1 || 0.1 A 600 V, DC-13, Q600 EN/IEC 60947-5-1 || 0.27 A 250 V, DC-13, Q600 EN/IEC 60947-5-1 || 0.55 A 125 V, DC-13, Q600 EN/IEC 60947-5-1 || 1.2 A 600 V, AC-15, A600 EN/IEC 60947-5-1
Positive Opening
with EN/IEC 60947-5-1 appendix K
Contacts Usage
low power switching contacts
Ambient Air Temperature For Operation
-40-70°C
Product Or Component Type
contact block
Mounting Of Block
front mounting
Operating Force
2 N NC changing electrical state
Contact Operation
slow-break
Short-Circuit Protection
10 A cartridge fuse gG EN/IEC 60947-5-1
Operating Travel
1.5 mm NC changing electrical state) || 4.3 mm total travel)
Shape Of Screw Head
cross pozidriv No 1 || slotted flat Ø 4 mm || slotted flat Ø 5.5 mm
Electrical Durability
1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C || 1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
Ip Degree Of Protection
IP5X
Contacts Type And Composition
1 NC
Electrical Composition Code
C9 3 ) || M5 2 ) || M9 2 )
Product Certifications
UL || GL || LROS (Lloyds register of shipping) || CCC || CSA || GOST || BV || DNV
[Uimp] Rated Impulse Withstand Voltage
6 kV EN 60947-1
Ambient Air Temperature For Storage
-40-70°C
[Ui] Rated Insulation Voltage
600 V 3)EN 60947-1
Range of Product
Harmony XB4, Harmony XB5
Country of Origin (subject to change)
France